BDL Környezetvédelmi Kft.

Xellia, design of industrial wastewater pre-treatment facility

Industrial wastewater treatment

2008: hydraulic capacity: Q = 340 m3/d

biological load: 816 kg BOI5/d

 

2010: hydraulic capacity: Q = 340 m3/d

biological load: 1530 kg BOI5/d

The existing wastewater treatment plant should have been intensified, because the owner, Xelia Pharmatuticals started  manufacturing a new product, and the organic contaminant part of the wastewater was predicted to double.

The cleaning line was the following: buffering, pH adjustment, mechanical cleaning, SBR type aerobe activated sludge technology.

The pre-treated wastewater gets discharged to the existing municipal sewer network.

As it is shown in the followings the technology can securely meet the requirements.

  limitation 2008. trial period average 2011. trial period average  
CODcr 1000 915 430 g/m3
BOD5 500 87 68 g/m3

 

1.jpg 2.jpg 3.jpg